This article is established for the safety and protection of the residents of Stockton, Kansas. It is also designed to mitigate the potential threat imposed by the installation of LP Gas within the City.
(Ord. 1588; Code 2015)
This article regulates:
(a) The installation of LP Gas within the City.
(b) Propane storage containers less than 125 gallons in size.
(c) Propane storage containers 125 to 250 gallons in size; and
(d) Propane storage containers 250 to 1,000 gallons in size.
Propane tanks must be located above ground level, i.e. no underground tanks are permitted. Propane tanks with a capacity greater than 1,000 gallons are prohibited.
(Ord. 1588; Code 2015)
The storage of LP Gas in closed containers or portable tanks (hereinafter tanks) on properties within the Stockton City Limits shall comply with the following standards:
(a) Containers less than 125 gallons in size. All of the above standards are applicable with the exception of the following (Note: Tanks that are 30 gallons or smaller and commonly used with barbecue grills and campers/RV’s fall under this category. Please note their exceptions below):
(1) City Notification. The owner is NOT required to submit a New LP-Gas Installation Application or pay an LP-Gas Permit Fee of $25.00 for containers of 30 gallons or less.
(2) Signage: It is not necessary for the owner to list their name, address and phone number on tanks less than 125 gallons in size. Tanks 30 gallons or less in size need not be labeled FLAMMABLE or LP-GAS, LPG, PROPANE or BUTANE.
(3) Location. There is no minimum distance that a tank can be mounted or placed alongside a home’s permanent structure(s). However, the tank must be a minimum of 10 feet from an intake, vent or A/C compressor and a minimum distance of 5 feet from a crawl space opening, window or exhaust fan (see container spacing diagram).
(4) Container Foundation. Containers of 30 gallons storage capacity or less are not required to be set on a concrete or steel foundation. However, they must be set on a stable, level foundation.
(5) Depth of pipelines. It is not necessary to bury pipelines, if the distance between the tank and the permanent home structure is two (2) feet or less or if the tank is placed on a mobile barbecue grill cart.
(b) Containers between 125 and 250 gallons in size:
(1) Containers. LP Gas tanks shall fully comply with all DOT/ICC or ASME standards.
(2) Signage. All tanks shall be painted and clearly marked FLAMMABLE and either LP-GAS, LPG, PROPANE or BUTANE in at least 3 inch, red letters. Also, the owner’s name, address and phone number displayed in at least 1 inch black letters.
(3) Location. Tanks must be located outside, in the back yard or rear section of the home or business and at least 10 feet away from the owner’s home, business, or permanent structures (i.e. garage, shed, etc.). Containers must be positioned at least 10 feet off of any street or alley and located no closer than 25 feet from another LP-Gas container on an adjacent property. Containers must be located at least 25 feet from a neighbor’s permanent structures in all directions. Where physical damage from vehicles is possible to LP-Gas containers or systems of which they are a part, precautions should be taken against such damage.
(4) Foundation. Tanks shall rest on either a concrete or substantial masonry support foundation. The foundation must be level. The owner must provide sufficient corrosion protection between the container and its saddle.
(5) Maintenance/Appearance. The owner shall properly maintain the tank and assure its safe operation. The tank shall be painted with a matte silver or flat white finish. The owner shall keep the ground below the container clear of dry grass and weeds.
(6) Pipe, Hose and Valves. All pipes and connections shall be tested and proven free of leaks by an LP Supplier prior to use by the owner. Pipes and connections shall comply with Schedule 40 Standards (for psi below 125). Pipes and connections shall comply with Schedule 80 Standards (for psi above 125). Galvanized pipe shall not be used. All hose and quick connectors shall be listed for LP-Gas use. Pressure relief valves, shut-off valves and back-flow valves shall be listed for such use. All liquid lines 1.5 inch or larger and vapor lines 1.25 inch or larger shall have an emergency shutoff valve.
(7) Depth of pipelines. All pipelines running between any permanent structure and the tank shall be buried underground to a minimum depth of eighteen (18) inches.
(8) City Notification. Prior to the installation of any LP-Gas tank on any property, the owner must contact the City Office, complete and submit a New LP-Gas Installation Application and pay a LP-Gas Permit Fee of $25.00.
(9) Inspection. After installation and prior to its use the owner must notify LP Supplier and have the installation inspected by a qualified LP employee.
(10) Zoning. Propane tanks between 125 and 250 gallons may be located in any zoning district, except Business which is in the Fire Limits of the City as established by Article 2 of Chapter VII of the Stockton City Code.
(c) Containers between 250 and 1,000 gallons in size:
(1) Containers. LP Gas tanks shall fully comply with all DOT/ICC or ASME standards.
(2) Signage. All tanks shall be painted and clearly marked FLAMMABLE and either LP-GAS, LPG, PROPANE or BUTANE in at least 3 inch, red letters. Also, the owner’s name, address and phone number displayed in at least 1 inch black letters.
(3) Location. Tanks must be located outside, in the back yard or rear section of the home or business and at least 25 feet away from the owner’s home, business, or permanent structures (i.e. garage, shed, etc.). Containers must be positioned at least 25 feet off of any street or alley and located no closer than 25 feet from another LP-Gas container on an adjacent property. Containers must be located at least 25 feet from a neighbor’s permanent structures in all directions. Where physical damage from vehicles is possible to LP-Gas containers or systems of which they are a part precautions should be taken against such damage.
(4) Foundation. Tanks shall rest on either a concrete or substantial masonry support foundation. The foundation must be level. The owner must provide sufficient corrosion protection between the container and its saddle.
(5) Maintenance/Appearance. The owner shall properly maintain the tank and assure its safe operation. The tank shall be painted with a matte silver or flat white finish. The owner shall keep the ground below the container clear of dry grass and weeds.
(6) Pipe, Hose and Valves. All pipes and connections shall be tested and proven free of leaks prior to use by the owner. Pipes and connections shall comply with Schedule 40 Standards (for psi below 125). Pipes and connections shall comply with Schedule 80 Standards (for psi above 125). Galvanized pipe shall not be used. All hose and quick connectors shall be listed for LP-Gas use. Pressure relief valves, shut-off valves and back-flow valves shall be listed for such use. All liquid lines 1.5 inch or larger and vapor lines 1.25 inch or larger shall have an emergency shutoff valve.
(7) Depth of pipelines. All pipelines running between any permanent structure and the tank shall be buried underground to a minimum depth of eighteen (18) inches.
(8) City Notification. Prior to the installation of any LP-Gas tank on any property, the owner must contact the City Office, complete and submit a New LP-Gas Installation Application and pay a LP-Gas Permit Fee of $25.00.
(9) Inspection. After installation and prior to its use the owner must notify the LP Supplier and have the installation inspected by a qualified LP Supplier employee.
(10) Pre-Existing Tanks. Any LP-Gas tanks in existence prior to the passage of this ordinance shall be required to meet the above standards within 6 months subsequent to the passage of this ordinance. The $25 application fee will NOT be charged for pre-existing containers.
(11) Zoning. Propane tanks between 250 and 1,000 gallons may ONLY be located in district zoned Agricultural and Industrial.
(Ord. 1588; Code 2015)
No propane tank shall be located within the Fire Limits of the City as established by Article 2 of Chapter VII of the Stockton City Code.
(Ord. 1588; Code 2015)
A violation of this article is a class B misdemeanor.
(Ord. 1588; Code 2015)